R Series Modular VRF Air Conditioner

 - Full DC-inverter VRF air conditioner, with Heat Recovery Function

 - R410a gas, high EER

- Power supply: 380~415V/3Ph/50Hz
- Modular outdoor units design:
  5 basic modules: 8HP, 10HP, 12HP, 14HP, and 16HP.
  Free combination of outdoor units
  Max capacity of combination up to 64HP(180kw)
- Wide operation temperature range: -20C~50C
- Stable cooling or heating performance

- Low noise

- Anti snow function, intelligent defrosting.
- Precise temperature control, room temperature fluctuation within 1C

Specification of Basic Modules

HP   8 10 12 14 16
Model Name  380~415V/3PH/50Hz CMV-R252W/ZR1 CMV-R280W/ZR1 CMV-R335W/ZR1 CMV-R400W/ZR1 CMV-R450W/ZR1
380~415V/3PH/60Hz CMV-R252W/YR1 CMV-R280W/YR1 CMV-R335W/YR1 CMV-R400W/YR1 CMV-R450W/YR1
Max. Connected indoor units quantity   13 16 20 23 26
Performance data            
Cooling Capacity KW 25.2 28.0 33.5 40.0 45.0
Btu/h 85000 95000 114000 136000 153000
RT 7.1 7.9 9.5 11.3 12.7
Power imput KW 5.70 6.62 8.03 11.02 13.08
EER W/W 4.42 4.23 4.17 3.63 3.44
Heating Capacity KW 27.4 31.5 37.5 45.0 50.0
Btu/h 93000 107000 127000 153000 170000
Power imput kW 5.88 7.19 8.80 11.00 12.63
COP W/W 4.66 4.38 4.26 4.09 3.96
Physical data            
Compressor  Quantity    1 2
Type    Hermatic scroll
Refrigerant Type    R410A
Throttle type   EXV
Volume Kg 12 16
Motor Type    DC motor
Quantity    2
ESP Pa 85
Dimension
 (W×H×D)
Net  mm 1260×765×1620
Packing mm 1315×825×1750
Net weight   kg 270 310
Sound pressure level   dB(A) 57 57 58 60 60
Piping data              
Refrigerant Piping Liquid Pipe mm Ø12.7 Ø12.7 Ø12.7 Ø15.9 Ø15.9
Low Pressure Gas Pipe mm Ø22.2 Ø22.2 Ø25.4 Ø28.6 Ø28.6
High Pressure Gas Pipe mm Ø19.1 Ø19.1 Ø19.1 Ø22.2 Ø22.2
High Pressure Gas Balance Pipe mm Ø19.1 Ø19.1 Ø19.1 Ø19.1 Ø19.1
Oil Balance Pipe mm Ø6.35 Ø6.35 Ø6.35 Ø6.35 Ø6.35

Notes:

1. Cooling operating temperature range is from -5°C to 50°C. Heating operating temperature range is from -20°C to 25°C,Simultaneous Cooling and Heating operating temperature range is from -5°C to 25°C

2. The cooling conditions: indoor side 27°C(80.6°F) DB, 19°C(60°F)WB outdoor side 35°C(95°F) DB

3. The heating conditions: indoor side 20°C(68°F) DB, 15°C(44.6°F)WB outdoor side 7°C(42.8°F)DB

4. Sound level: measured at a point 1 m in front of the unit at a height of 1.3 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions.

5. The above data may be changed without notice for future improvement on quality and performance.

6. Piping length: Interconnecting piping length is 7.5m(24.6ft), level difference is zero.

7. Connection piping diameter is based on the condition that the total equivalent liquid length is less than 90m(295.2ft). When the total equivalent liquid length is more than 90m(295.2ft), please refer to technical manual to choose the connection piping diameter.