Mini VRF air conditioner

- DC-inverter, R410a gas

- Power supply: 220~240V/1Ph/50Hz, 380~415V/3Ph/50Hz

                           220~240V/1Ph/60Hz, 380~415V/3Ph/60Hz

 

- Capacity: 8kw to 26kw, 8 models

- Wide operation temperature range: -20C~50C
- Stable cooling or heating performance

- Low noise

- Anti snow function, intelligent defrosting.

8kw, 10kw mini VRF, VRV air conditioner

8/10kw Mini VRF

12.5kw to 18kw mini VRF, VRV air conditioner

12.5/14/16/18kw Mini VRF

22.4kw, 26kw mini VRF, VRV air conditioner

22.4/26kw Mini VRF


Specification 220~240V/1Ph/50Hz 

Model Name CMV-V080W/R1 CMV-V100W/R1 CMV-V125W/R1 CMV-V140W/R1 CMV-V160W/R1
Power 220V-240V/1PH/50HZ 220V-240V/1PH/50HZ 220V-240V/1PH/50HZ 220V-240V/1PH/50HZ 220V-240V/1PH/50HZ
Max. Connected indoor units quantity 4 5 6 7 8
Performance data            
Cooling Capacity KW 8 10 12.5 14 16
Btu/h 27300 34000 42000 47000 54000
RT 2.3 2.8 3.5 4.0 4.5
Power imput KW 2.15 2.68 3.38 3.96 4.57
EER W/W 3.72 3.70 3.69 3.52 3.50
Heating Capacity KW 9 11 14 16 18
Btu/h 30700 38000 47000 54000 61000
RT 2.6 3.1 4.0 4.5 5.2
Power imput kW 2.28 2.8 3.65 4.3 5.13
COP W/W 3.95 3.93 3.83 3.72 3.61
Max.input consumption KW 4.00 4.00 6.30 6.30 6.30
Max.current A 18.00 18.0 28.0 28.0 28.0
Capacity adjustment range   50%-130% 50%-130% 50%-130% 50%-130% 50%-130%
Physical data              
Compressor  Quantity    1 1 1 1 1
Type    DC /Twin-rotary DC /Twin-rotary DC /Twin-rotary DC /Twin-rotary DC /Twin-rotary
Refrigerant Type    R410A R410A R410A R410A R410A
Volume g 3000 3000 3100 3450 4200
Motor Type    Axial Axial Axial Axial Axial
Quantity    1 1 2 2 2
Dimension
 (W×H×D)
Net  mm 1054×994×399 1054×994×399 900×1328×345 900×1328×345 900×1328×345
Packing mm 1145×1120×475 1145×1120×475 964x1445x402 964x1445x402 964x1445x402
weight Net  kg 80 80 89 89 96
Gross kg 92 92 100 100 107
Sound pressure level dB(A) 56
56
56 58
58
Max operation pressure Mpa 3.8 3.8 3.8 3.8 3.8
Piping& wiring data            
Pipe size Liquid pipe  mm φ9.53(flaring nut) φ9.53(flaring nut) φ9.53(flaring nut) φ9.53(flaring nut) φ9.53(flaring nut)
Gas pipe mm φ15.9(flaring nut) φ15.9(flaring nut) φ15.9(flaring nut) φ15.9(flaring nut) φ15.9(flaring nut)

Specification 380~415V/3Ph/50Hz

Model Name CMV-V125W/ZR1 CMV-V140W/ZR1 CMV-V160W/ZR1 CMV-V180W/ZR1 CMV-VH224W/ZR1 CMV-VH260W/ZR1
Power 380V-415V/3PH/50HZ 380V-415V/3PH/50HZ 380V-415V/3PH/50HZ 380V-415V/3PH/50HZ 380V-415V/3PH/50HZ 380V-415V/3PH/50HZ
Max. Connected indoor units quantity 6 7 8 9 10 12
Performance data              
Cooling Capacity KW 12.5 14 16 18 22.4 26
Btu/h 42000 47000 54000 61000 76500 88700
RT 3.5 4.0 4.5 5.2 6.4 7.4
Power imput KW 3.38 3.98 4.58 5.19 6.74 7.54
EER W/W 3.69 3.52 3.50 3.47 3.32 3.45
Heating Capacity KW 14 16 18 20 25 28.5
Btu/h 47000 54000 61000 68000 85300 97300
RT 4.0 4.5 5.2 5.7 7.1 8.1
Power imput kW 3.66 4.3 5.13 5.62 5.85 6.77
COP W/W 3.83 3.72 3.61 3.56 4.27 4.21
Max.input consumption KW 6.30 6.30 6.30 7 10.2 10.5
Max.current A 10.00 10.00 10.00 12.5 16.5 18.5
Capacity adjustment range   50%-130% 50%-130% 50%-130% 50%-130% 50%-130% 50%-130%
Physical data                
Compressor  Quantity    1 1 1 1 1 1
Type    DC /Twin-rotary DC /Twin-rotary DC /Twin-rotary DC /Twin-rotary DC /Twin-rotary DC /Twin-rotary
Refrigerant Type    R410A R410A R410A R410A R410A R410A
Volume g 3100 3450 4200 4550 6100 6100
Motor Type    Axial Axial Axial Axial Axial Axial
Quantity    2 2 2 2 2 2
Dimension
 (W×H×D)
Net  mm 900×1328×345 900×1328×345 900×1328×345 900×1328×345 1120*1549*528 1120*1549*528
Packing mm 964x1445x402 964x1445x402 964x1445x402 964x1445x402 1278*1696*560 1278*1696*560
weight Net  kg 93 93 100 102 145 145
Gross kg 104 104 111 112 165 165
Sound pressure level dB(A) 56 58 58
≤58 ≤58 60
Max operation pressure Mpa 3.8 3.8 3.8 3.8 3.8 3.8
Piping& wiring data              
Pipe size Liquid pipe  mm φ9.53(flaring nut) φ9.53(flaring nut) φ9.53(flaring nut) φ9.53(flaring nut) φ9.53(flaring nut) φ9.53(flaring nut)
Gas pipe mm φ15.9(flaring nut) φ15.9(flaring nut) φ15.9(flaring nut) φ15.9(flaring nut) φ22.2(Welding) φ22.2(Welding)

Notes:

1. Cooling operating temperature range is from -5°C to 50°C. Heating operating temperature range is from -20°C to 30°C

2. The cooling conditions: indoor side 27°C(80.6°F) DB, 19°C(60°F)WB outdoor side 35°C(95°F) DB

3. The heating conditions: indoor side 20°C(68°F) DB, 15°C(44.6°F)WB outdoor side 7°C(42.8°F)DB

4. Sound level: measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions.

5. The above data may be changed without notice for future improvement on quality and performance.